other
  • Winter Usage Guidelines for Industrial Chillers Jan 26, 2026
    During winter, low ambient temperatures pose several challenges for chillers. Proper usage and maintenance are essential to ensure stable operation, extend the equipment's lifespan, and reduce operational costs. Hengde, a leader in the refrigeration equipment industry, has extensive experience in the research, production, and maintenance of chillers. Below are the key points and maintenance guidelines for industrial chiller use in winter, based on Hengde’s expert advice.   1. Pre-Startup Key Checks Water System Inspection Winter temperatures can cause water to freeze, so it’s crucial to thoroughly check both the cooling and chilled water systems. Ensure the water level is normal, and that the water is clear and free from impurities. If the water quality is poor, it should be treated or replaced. Additionally, inspect the water system's filters, clean or replace the filter elements to ensure smooth water flow and prevent ice blockages in the pipes.   Insulation measures inspection Check whether the insulation layer of each component of the industrial chiller is intact, especially the pipes and water tanks. If the insulation layer is damaged, the heat loss of the equipment will accelerate in a low temperature environment, energy consumption will increase, and the water system may also freeze. If damage is found, it is necessary to repair or replace the insulation material in time.   Electrical System Pre-Inspection Quickly check the electrical wiring for visible damage and ensure that terminal connections are secure. Verify that the power supply voltage is stable and within the chiller's rated voltage range. Hengde industrial chillers are equipped with an intelligent voltage monitoring system, but a manual inspection can help identify potential issues before they arise.   2. Operating Precautions Insulation measures inspection Check whether the insulation layer of each component of the chiller is intact, especially the pipes and water tanks. If the insulation layer is damaged, the heat loss of the equipment will accelerate in a low temperature environment, energy consumption will increase, and the water system may also freeze. If damage is found, it is necessary to repair or replace the insulation material in time.   Monitor Temperature Fluctuations In winter, the lower ambient temperature reduces the cooling load on the industrial chiller. It’s essential to closely monitor the temperatures of the evaporator, condenser, as well as the outlet temperatures of industrial chilled and cooling water. Based on these readings, adjust the operational parameters accordingly to prevent prolonged low-load operation, which can reduce compressor efficiency and increase energy consumption. Hengde industrial chillers feature an intelligent control system that automatically adjusts based on temperature fluctuations, ensuring efficient operation.   Insulation measures inspection Check whether the insulation layer of each component of the industrial chiller is intact, especially the pipes and water tanks. If the insulation layer is damaged, the heat loss of the equipment will accelerate in a low temperature environment, energy consumption will increase, and the water system may also freeze. If damage is found, it is necessary to repair or replace the insulation material in time.    Prevent Ice Formation In cold weather, the risk of water system freezing is higher. To prevent freezing, add an appropriate amount of antifreeze to the water, and ensure that the water system circulates properly. If any signs of freezing are detected, immediately shut down the system, thaw it, and restart it only after ensuring the water flow is restored.   Hengde not only offers high-performance industrial chillers but also provides comprehensive technical support and after-sales services. During winter operations, Hengde’s expert technical team is available to offer remote or on-site guidance, helping users solve any issues they may encounter. Hengde also conducts regular follow-up visits to check the equipment's operation, offering targeted maintenance suggestions to ensure the industrial water cooled chiller and air cooled chiller run efficiently and reliably throughout the winter.   Choose Hengde, Choose Perfect Industrial Chillers!
  • Why Does My Chiller Have a Three-Phase Power Fault? Causes and Solutions Sep 04, 2026
    A three-phase power fault is a common alarm found on industrial chillers, especially three-phase air-cooled and water-cooled chiller systems. When this alarm appears, the chiller may fail to start, the compressor may not run, or the controller may immediately stop the unit for protection.   For technicians and after-sales teams, the important point is that a three-phase power fault does not necessarily mean the chiller itself is defective. The problem may come from the factory power supply, wiring, phase sequence, protection devices, or even changes in the electrical environment around the machine. This guide explains how to troubleshoot the problem from the easiest checks to the more technical ones. What Does a Three-Phase Power Fault Mean? A three-phase chiller normally needs three-phase voltage within the specified operating range. The control system monitors the incoming power before allowing major components such as the compressor to start. If the controller detects conditions such as: Phase loss Incorrect phase sequence Overvoltage Undervoltage Large voltage imbalance Abnormal incoming power Power protection device failure the industrial chiller may display a three-phase power fault or similar alarm.   The exact alarm name varies between chiller manufacturers and controller types, so technicians should always check the electrical diagram and manual for the specific model. Common Causes of Three-Phase Power Faults 1. No or Poor Incoming Power Start with the simplest possibility. Check whether the factory power supply is actually available. Then inspect the main breaker, isolator, terminal connections and incoming cable.   A loose terminal can create intermittent contact. The chiller may work normally one day and suddenly report a power fault the next.   Solution: With the power safely isolated, inspect and tighten electrical connections according to the manufacturer's requirements. Damaged cables, plugs, breakers or terminals should be replaced rather than temporarily repaired.   2. Phase Loss A three-phase chiller can receive power on only two phases if a fuse, breaker, cable or terminal connection fails. For example, a system may measure normal voltage between two phases but show an abnormal reading on the third phase.This is why checking only one voltage measurement is not enough.   Solution: A qualified electrician should measure all three phase-to-phase voltages and compare them with the chiller's specified supply range. If one phase is missing, trace the circuit from the distribution panel to the chiller input.   3. Voltage Imbalance or Unstable Factory Power Even when all three phases are present, the voltage may not be balanced.   Large voltage differences between phases can cause excessive current and overheating in three-phase motors and compressors. Some chillers will therefore stop before the compressor starts.   Solution: Measure the three-phase voltage while the electrical system is under realistic operating conditions. If the voltage fluctuates significantly, investigate the factory power supply, transformer, distribution system, or other heavy electrical loads.   Hengde Insight:Don't check voltage only when the factory is quiet. A power supply that looks normal at 8 a.m. may behave differently when large motors, welding machines, compressors or production equipment start working. For difficult cases, monitoring the voltage during actual production can reveal problems that a single measurement misses.   4. Incorrect Phase Sequence Some three-phase chillers use a phase-sequence protection device. If the incoming phases are connected in the wrong order, the controller may prevent the compressor from starting.This can happen after electrical installation, maintenance or relocation.   Solution: A qualified electrician should verify the phase sequence with the appropriate test instrument. If it is incorrect, the wiring should be corrected only after the power has been isolated and according to the electrical diagram and local electrical requirements.   Do not randomly swap wires while the equipment is energized.   5. Faulty Phase Protection Relay The chiller itself may have normal incoming power, but the phase protection relay or monitoring device may malfunction.A damaged relay can incorrectly detect phase loss, abnormal voltage or phase sequence and prevent the machine from starting.   Solution: Measure the actual incoming voltage first. If the power is normal but the protection relay reports an abnormal condition, the relay and its wiring should be tested by qualified personnel and replaced if necessary.   6. Loose or Oxidized Electrical Terminals This problem deserves more attention than it usually gets. Industrial chillers operate for long periods under vibration and electrical load. Over time, terminal connections can become loose or develop oxidation, increasing electrical resistance.   The result may be heat buildup, unstable contact and intermittent power alarms.   Solution: Inspect the main terminals, contactors, breakers and control-circuit connections during scheduled maintenance. Look for discoloration, overheating marks or damaged insulation.   Hengde Insight:A power fault that appears “randomly” is often more interesting than a fault that appears every time the machine starts. Intermittent alarms should make technicians think about connections, heat and vibration, rather than immediately assuming that the controller has failed.   A Practical Troubleshooting Sequence For after-sales technicians, we recommend following a simple order: Power available → Main breaker → Three-phase voltage → Phase balance → Phase sequence → Terminals → Protection relay → Control transformer → Chiller controller   This prevents unnecessary replacement of expensive components.  For example, replacing a controller before checking the incoming power can solve nothing if the actual problem is a factory breaker or loose terminal. A Representative Hengde After-Sales Case A customer using a Hengde Air Cooled Chiller reported that the machine suddenly displayed a three-phase power fault and could not start. The customer initially suspected that the chiller's electrical system had failed. Hengde's technical team first asked the customer to check the incoming power rather than immediately opening the industrial chiller. The technician guided the customer through several checks. The chiller's three-phase supply was eventually found to be abnormal because of a problem with the factory-side electrical breaker.   After the breaker was repaired and the incoming power returned to normal, the alarm disappeared and the chiller restarted normally. The lesson is simple: the location of an alarm is not always the location of the problem.   For an industrial chiller, the three-phase protection circuit is monitoring the electrical conditions supplied to the machine. Therefore, the factory distribution system should always be included in the troubleshooting process. Advice for Buyers, Technicians and After-Sales Teams When purchasing a three-phase industrial chiller, buyers should confirm the required voltage, phase and frequency before placing the order.   For technicians, record the actual voltage, alarm code and operating conditions before replacing components.   For after-sales teams, ask the customer a few basic questions first: Did the fault appear suddenly or gradually? Are other machines experiencing power problems? Was there recent electrical maintenance? Was the chiller recently moved or rewired? Does the alarm disappear after restarting? Is the incoming three-phase voltage normal? These questions can significantly shorten troubleshooting time. Final Thoughts A three-phase power fault should not automatically be treated as a chiller failure. In many cases, the root cause is somewhere between the factory power supply and the chiller's electrical protection circuit.   The most efficient troubleshooting method is to work from the outside in: check the power first, then the protection devices, and only then investigate the chiller's internal electrical components.   If the cause cannot be confirmed, it is safer to stop the machine and contact the industrial chiller manufacturer or a qualified electrician rather than repeatedly restarting the equipment. This protects both the Industrial Chiller and the people working around it.

Need Help? Chat with us

leave a message
For any request of information or technical support, fill in the form. All fields marked with an asterisk (*) are required.
Submit

Home

Products

whatsApp

contact